Kľúčové špecifikácie
: 58 W (48 V DC)
Depth: 26.3 mm
Width: 12.6 mm
Height: 29 mm
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
58 W (48 V DC)
Depth 26.3 mm
Width 12.6 mm
Height 29 mm
General The outputs are not suitable for switching different outer conductors.
Altitude ≤ 2000 m
Insulation Basic insulation
Application Forcibly guided contacts
Coil voltage 24 V DC
Typ produktu Single relay
Mounting type Plug-in mounting
Operating mode 100% operating factor
Status display Yellow LED
Test voltage () 1.5 kVrms(50 Hz, 1 min.)
Contact material AgSnO
Drive (polarity) non-polarized
Pollution degree 2
Cross section AWG (converted acc. to IEC)
Mounting position any
Drive and function monostable
Protective circuit Freewheeling diode
Input voltage range 19.2 V DC ... 26.4 V DC
Rated surge voltage 4 kV
Overvoltage category III
Typical release time 10 ms
Assembly instructions in rows with zero spacing
Standards/regulations EN 61810-1
Typical response time 15 ms
Contact switching type 2 changeover contacts, forcibly actuated
Type of switch contact Single contact
Mechanical service life approx. 107cycles
Nominal input voltage UN 24 V DC
Rated insulation voltage 250 V AC
Maximum switching voltage 250 V AC/DC
Limiting continuous current 6 A
Typical input current at UN 30 mA
Degree of protection (Relay) RT II (Relay)
Input power dissipation for UN 0.72 W
Test voltage (Winding/contact) 4 kVrms(50 Hz, 1 min.)
Ambient temperature (operation) -25 °C ... 60 °C
Interrupting rating (ohmic load) max. 144 W (24 V DC)
Input voltage range in reference to UN see diagram
Ambient temperature (storage/transport) -25 °C ... 85 °C
Degree of protection (Installation location) IP54 (Installation location)
Maximum power dissipation for nominal condition 0.7 W
Force-guided contacts in accordance with EN 61810-3 Type B
Test voltage (Changeover contact/changeover contact) 2.5 kVrms(50 Hz, 1 min.)

Popis produktu

Safety relay with force-guided contacts in accordance with DIN EN 61810-3, contact switching type: 2 changeover contacts. The requirements for type A in accordance with DIN EN 61810-3 are satisfied if
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top