Čas služby: pondelok až piatok 9:00-18:00
BC 17 REL-S/MSTB/R3,3K/R680 - BC 17 REL-S/MSTB/R3,3K/R680 2900116 PHOENIX CONTACT Relay Module
Na sklade Horúci produkt

BC 17 REL-S/MSTB/R3,3K/R680

BC 17 REL-S/MSTB/R3,3K/R680 2900116 PHOENIX CONTACT Relay Module

$0.00 USD
3131 na sklade
Kľúčové špecifikácie
GTIN: 4046356473705
Orderkey: 2900116
Depth (Note): 61 mm
Packing unit: 1
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4046356473705
Orderkey 2900116
Depth (Note) 61 mm
Packing unit 1
Width (Note) 17.8 mm
Height (Note) 90 mm
Note (Coil side) A 680 Ω resistor is connected in series and a 3.3 kΩ resistor is connected parallel to the output
Custom tariff number 85364190
(Ambient conditions) Capacitor Capacitor
Designation (General) Air clearances and creepage distances, input/output
Contact type (Coil side) 1 N/C contact
(Standards and Regulations) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Contact material (Coil side) AgSnO2, gold-plated
Degree of pollution (General) 2
Rated surge voltage (General) 4 kV (1.2/50 μs)
Overvoltage category (General) III
Net weight (SAP) (Contact side) 64.85 g
Standards/regulations (General) EN 50178
Mounting position (Contact side) any
Rated insulation voltage (General) 250 V
Degree of protection (Contact side) IP20
Assembly instructions (Contact side) In rows with zero spacing
Maximum switching voltage (Coil side) 30 V AC
China RoHS (Standards and Regulations) Environmentally Friendly Use Period = 50
Limiting continuous current (Coil side) max. 3 A
Protective circuit (Ambient conditions) Bridge rectifier Bridge rectifier, varistor
Rated surge voltage/insulation (General) Basic insulation
Ambient temperature (operation) (Dimensions) -20 °C ... 50 °C
Nominal input voltage UN (Ambient conditions) 24 V DC
Utilization restriction (Key Commercial Data) EMC: class A product, see manufacturer's declaration in the download area
Operating voltage display (Ambient conditions) LED
Typical input current at UN (Ambient conditions) 10 mA
Input voltage range in reference to UN (Ambient conditions) 0.8 ... 1.1

Popis produktu

Relay module, standard interfaces for fire detection systems with soldered miniature relays, 1 closed contact, input voltage 24 V DC
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top