Čas služby: pondelok až piatok 9:00-18:00
TTC-6P-1X2-EX-24DC-UT-I - TTC-6P-1X2-EX-24DC-UT-I 1065312 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele..
Na sklade Horúci produkt

TTC-6P-1X2-EX-24DC-UT-I

TTC-6P-1X2-EX-24DC-UT-I 1065312 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele..

$0.00 USD
3601 na sklade
Kľúčové špecifikácie
: C2
Note: 2018
Type: DIN rail module, two-section, divisible
Color: blue (RAL 5015)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
C2
Note 2018
Type DIN rail module, two-section, divisible
Color blue (RAL 5015)
Depth 100 mm (incl. DIN rail 7.5 mm)
Width 6.2 mm +0.1 mm
Height 105.8 mm
Altitude ≤ 2000 m (amsl)
Typ produktu Surge protection for MCR technology
Screw thread M3
Mounting type DIN rail: TH 35 - 7.5 mm
Rated current 600 mA (40 °C)
Product family TERMITRAB complete
Open side panel No
Article revision 10
Housing material PBT
Pollution degree 2
UL, USA / Canada Class I, Div. 2, Groups A, B, C, D T4A
Connection method Screw connection
Tightening torque 0.5 Nm ... 0.6 Nm
Nominal voltage UN 24 V DC
Dimensional drawing
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Insulating material PBT
Resistance per path 1.65 Ω ±20 %
Capacity (Core-Core) typ. 2 nF
Degree of protection IP20
Overvoltage category III
Residual current IPE ≤ 1 µA
Max. input current Ii 400 mA (T4 / -40 °C ... +50 °C)
Max. input voltage Ui 30 V DC
Wire pairs per module 1
IEC test classification C1
Standards/specifications EN 60079-0
Input attenuation aE, sym. typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Max. required back-up fuse 630 mA (FF)
Conductor cross section AWG 24 ... 12
Max. internal inductance Li negligible
Response time tA(line-line) ≤ 1 ns
Insulation voltage to ground > 180 V DC
Maximum inner capacitance Ci negligible
Pulse reset time (line-line) ≤ 700 ms
Response time tA(line-earth) ≤ 100 ns
Conductor cross section rigid 0.2 mm² ... 4 mm²
Maximum continuous voltage UC 30 V DC
Pulse reset time (line-earth) ≤ 30 ms
Impulse durability (line-line) C1 - 1 kV / 500 A
Surge protection fault message optical
Ambient temperature (operation) -40 °C ... 70 °C (with current derating)
Impulse durability (line-earth) C1 - 1 kV / 500 A
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Permissible humidity (operation) 5 % ... 95 %
Operating effective current ICat UC ≤ 5 µA
Flammability rating according to UL 94 V-0
Voltage protection level Up(line-line) ≤ 55 V (C1 - 1 kV / 500 A)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Voltage protection level Up(line-earth) ≤ 900 V (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs 10 kA
Voltage protection level Upstatic (line-line) ≤ 50 V (C1 - 1 kV / 500 A)
Voltage protection level Upstatic (line-earth) ≤ 900 V (C1 - 1 kV / 500 A)
Nominal discharge current In(8/20) µs (line-line) 5 kA
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 940 kHz
Nominal discharge current In(8/20) µs (line-ground) 5 kA
Pulse discharge current Iimp(10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth) 0.5 kA

Popis produktu

Surge protection, consisting of plug-in protection and base element, with integrated status indication for a potential-free 2-wire intrinsically safe signal circuit, e.g. 0(4) current loop... 20 mA, s
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top