Čas služby: pondelok až piatok 9:00-18:00
STEP-PS/ 1AC/24DC/1.75 - STEP-PS/ 1AC/24DC/1.75 2868648 PHOENIX CONTACT Power supply unit
Na sklade Horúci produkt

STEP-PS/ 1AC/24DC/1.75

STEP-PS/ 1AC/24DC/1.75 2868648 PHOENIX CONTACT Power supply unit

$0.00 USD
4638 na sklade
Kľúčové špecifikácie
: 95 V DC ... 250 V DC
CSA: CSA-C22.2 No. 107.1-01
Input: 4 kV (Test Level 4 - asymmetrical)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
95 V DC ... 250 V DC
CSA CSA-C22.2 No. 107.1-01
Input 4 kV (Test Level 4 - asymmetrical)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width 54 mm
Height 90 mm
Output 2 kV (Test Level 3 - asymmetrical)
Voltage 3 V (Test Level 2)
Comments Criterion A
Derating 55 °C ... 70 °C (2.5 %/K)
Rise time < 0.5 s (UOUT(10 % ... 90 %))
Temp code T4A (70 °C)
Efficiency > 89 % (for 230 V AC and nominal values)
Input fuse 3.15 A (slow-blow, internal)
Output power 42 W
Typ produktu Power supply
Screw thread M3
UL approvals UL/C-UL listed UL 508
Assembly note alignable: 0 mm horizontally, 30 mm vertically
Mounting type DIN rail mounting
Climatic class 3K3 (in acc. with EN 60721)
Inrush current < 15 A (typical)
Product family STEP POWER
Status display "DC OK" LED green
Frequency range 80 MHz ... 1 GHz
Residual ripple < 60 mVPP(20 MHz)
Article revision 05
Discharge in air 8 kV (Test Level 3)
Horizontal pitch 3 Div.
Housing material Plastic
Number of phases 1.00
Protection class II (in closed control cabinet)
Stripping length 6.5 mm
Connection method Screw connection
Contact discharge 6 kV (Test Level 3)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Mounting position horizontal DIN rail NS 35, EN 60715
Rail applications EN 50121-4
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Protective circuit Transient surge protection; Varistor
Types of signaling LED
Current consumption 0.6 A (120 V AC)
Degree of pollution 2
Dimensional drawing
Foot latch material POM (Polyoxymethylene)
Input voltage range 85 V AC ... 264 V AC
Output current Imax 3.75 A
Short-circuit-proof yes
Test field strength 10 V/m
Connection in series yes
Degree of protection IP20
Mains buffering time typ. 25 ms (120 V AC)
Overvoltage category III
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Output characteristic U/I
Shipbuilding approval DNV GL (EMC B) ABS, NK
Standards/regulations EN 61000-4-2
Tightening torque max 0.6 Nm
Typical response time < 0.5 s
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Connection in parallel yes, for redundancy and increased capacity
Input voltage range AC 85 V AC ... 264 V AC
Input voltage range DC 95 V DC ... 250 V DC
Nominal output voltage 24 V DC
Note on status display UOUT> 21.5 V: LED lights up
Power factor (cos phi) 0.57
Tightening torque, min 0.5 Nm
With protective coating no
Nominal power consumption 84.2 VA
Operating voltage display Green LED
Standard - Safe isolation DIN VDE 0100-410
MTBF (IEC 61709, SN 29500) > 1569000 h (40 °C)
Feedback voltage resistance ≤ 35 V DC
Nominal input voltage range 100 V AC ... 240 V AC
Nominal output current (IN) 1.75 A (-25 °C ... 55 °C)
Power loss nominal load max. 5 W
Standard - Electrical safety IEC 62368-1 (SELV)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Inrush current integral (I2t) < 0.6 A2s
Insulation voltage input / PE 3.5 kV AC (type test)
Insulation voltage output / PE 500 V DC (routine test)
Voltage type of supply voltage AC/DC
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Insulation voltage input/output 4 kV AC (type test)
Conductor cross section AWG max. 12
Conductor cross section AWG min. 24
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 30 mm / 30 mm
SIL in accordance with IEC 61508 0
Maximum no-load power dissipation < 0.7 W
Standard - Safety of transformers EN 61558-2-16
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section, rigid min. 0.2 mm²
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise immunity EN 61000-6-1
Peak switching voltages nominal load < 40 mVPP(20 MHz)
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)
Depth Device depth (DIN rail mounting) 55 mm (Device depth (DIN rail mounting))
Ambient temperature (storage/transport) -40 °C ... 85 °C
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Setting range of the output voltage (USet) 22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
Protection against overvoltage at the output (OVP) < 35 V DC
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)

Popis produktu

STEP POWER Primary Switch-On Power Supply for Rail Mounting, Input: Single Phase, Output: 24 V DC/1.75 A
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top