Čas služby: pondelok až piatok 9:00-18:00
QUINT4-PS/1AC/12DC/2.5/PT - QUINT4-PS/1AC/12DC/2.5/PT 2904605 PHOENIX CONTACT Primary-switched power supply unit, QUINT POWER, Push-in c..
Na sklade Horúci produkt

QUINT4-PS/1AC/12DC/2.5/PT

QUINT4-PS/1AC/12DC/2.5/PT 2904605 PHOENIX CONTACT Primary-switched power supply unit, QUINT POWER, Push-in c..

$0.00 USD
4520 na sklade
Kľúčové špecifikácie
GTIN: 4055626255736
Orderkey: 2904605
(Drawings):
(Standards): ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4055626255736
Orderkey 2904605
(Drawings)
(Standards) ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Catalog page Page 252 (C-4-2019)
Packing unit 1 pc
(Input data) < 3 W (230 V AC)
(Output data) > 459000 h (60 °C)
SIQ (Standards) CB-Scheme (IEC 61010-1, IEC 61010-2-201)
Depth (Drawings) 90 mm
Width (Drawings) 22.5 mm
Country of origin DE (Germany)
ETIM 5.0 (eCl@ss) EC002540
ETIM 6.0 (eCl@ss) EC002540
ETIM 7.0 (eCl@ss) EC002540
Height (Drawings) 106 mm
Diagram (Drawings)
UNSPSC 13.2 (ETIM) 39121004
UNSPSC 18.0 (ETIM) 39121004
UNSPSC 19.0 (ETIM) 39121004
UNSPSC 20.0 (ETIM) 39121004
UNSPSC 21.0 (ETIM) 39121004
Custom tariff number 85044030
(Ambient conditions) typ. 54 ms (230 V AC)
(Conformance/approvals) 1 kV (symmetrical)
Block diagram (Drawings)
Efficiency (Output data) typ. 89.5 % (120 V AC)
Net weight (Output data) 0.181 kg
UL approvals (Standards) UL Listed UL 61010-1
Output power (Input data) 30 W
Stripping length (General) 10 mm
Climatic class (Dimensions) 3K3 (in acc. with EN 60721)
Connection method (General) Push-in connection
Residual ripple (Input data) < 30 mVPP(with nominal values)
eCl@ss 5.1 (Classifications) 27242213
eCl@ss 6.0 (Classifications) 27049000
eCl@ss 7.0 (Classifications) 27049002
eCl@ss 8.0 (Classifications) 27049002
eCl@ss 9.0 (Classifications) 27040701
I/O/S (Conformance/approvals) asymmetrical
Input (Conformance/approvals) 2 kV (symmetrical)
Control deviation (Input data) < 0.2 % (Static load change 10 % ... 90 %)
Output (Conformance/approvals) 1 kV (Test Level 3 - symmetrical)
Protection class (Output data) II
Signal (Conformance/approvals) 0.5 kV (Test Level 2 - symmetrical)
Flicker (Conformance/approvals) EN 61000-3-3
Input fuse (Ambient conditions) 3.15 A (slow-blow, internal)
Voltage (Conformance/approvals) 1 kV (symmetrical)
(Connection data for signaling) IEC 61010-2-201 (PELV)
Comments (Conformance/approvals) Criterion A
Degree of pollution (Dimensions) 2
Installation height (Dimensions) ≤ 5000 m (> 2000 m, observe derating)
Connection in series (Input data) yes
Degree of protection (Dimensions) IP20
Frequency (Conformance/approvals) 60 Hz
Degree of protection (Output data) IP20
Typical response time (Input data) 500 ms
Connection in parallel (Input data) Yes, for redundancy and increased capacity
Criterion A (Conformance/approvals) Normal operating behavior within the specified limits.
Criterion B (Conformance/approvals) Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C (Conformance/approvals) Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Inrush current (Ambient conditions) typ. 11.3 A (at 25 °C)
Nominal output voltage (Input data) 12 V DC
Voltage dip (Conformance/approvals) 0 %
Test level 1 (Conformance/approvals) 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Test level 2 (Conformance/approvals) 16.67 Hz 50 Hz 60 Hz (Test Level 2)
Voltage dips (Conformance/approvals) EN 61000-4-11
Weight per Piece (excluding packing) 240.000 g
Noise emission (Conformance/approvals) EN 55016
Additional text (Conformance/approvals) Test Level 2
Dynamic Boost (IDyn.Boost) (Input data) 4.5 A (≤ 60 °C (5 s))
Frequency range (Conformance/approvals) 0.15 MHz ... 80 MHz
Static Boost (IStat.Boost) (Input data) 3.125 A (≤ 40 °C)
Type of protection (Ambient conditions) Transient surge protection
Current consumption (Ambient conditions) 0.44 A (100 V AC)
Discharge in air (Conformance/approvals) 15 kV (Test Level 4)
Feedback voltage resistance (Input data) ≤ 25 V DC
Input voltage range (Ambient conditions) 100 V AC ... 240 V AC -15 % ... +10 %
MTBF (IEC 61709, SN 29500) (Output data) > 1848000 h (25 °C)
Nominal output current (IN) (Input data) 2.5 A
Contact discharge (Conformance/approvals) 8 kV (Test Level 4)
Frequency range (fN) (Ambient conditions) 50 Hz ... 60 Hz -10 % ... +10 %
Harmonic currents (Conformance/approvals) EN 61000-3-2
Mains buffering time (Ambient conditions) typ. 54 ms (120 V AC)
Number of periods (Conformance/approvals) 0.5 / 1 / 5 / 50 periods
Power loss nominal load max. (Input data) < 3.5 W (120 V AC)
Stripping length (Connection data, input) 10 mm
Conductor cross section AWG max. (General) 14
Conductor cross section AWG min. (General) 24
Connection method (Connection data, input) Push-in connection
Stripping length (Connection data, output) 10 mm
Connection method (Connection data, output) Push-in connection
Test field strength (Conformance/approvals) 1000 A/m
Ambient temperature (operation) (Dimensions) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Conductor cross section solid max. (General) 2.5 mm²
Conductor cross section solid min. (General) 0.2 mm²
Discharge current to PE (Ambient conditions) < 0.25 mA (264 V AC, 60 Hz)
Insulation voltage input/output (Output data) 4 kV AC (type test)
Nominal power consumption (Ambient conditions) 32.8 VA
Conductor cross section flexible max. (General) 2.5 mm²
Conductor cross section flexible min. (General) 0.2 mm²
Electrostatic discharge (Conformance/approvals) EN 61000-4-2
Fast transients (burst) (Conformance/approvals) EN 61000-4-4
Conducted noise emission (Conformance/approvals) EN 55016
Dielectric strength maximum (Ambient conditions) 300 V AC 60 s
Electromagnetic HF field (Conformance/approvals) EN 61000-4-3
Protective circuit/component (Ambient conditions) Varistor
Pulse-shape magnetic field (Conformance/approvals) EN 61000-4-9
Surge voltage load (surge) (Conformance/approvals) EN 61000-4-5
Attenuated oscillating wave (Conformance/approvals) EN 61000-4-18
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 85 °C
Electromagnetic compatibility (Conformance/approvals) Conformance with EMC Directive 2014/30/EU
Setting range of the output voltage (USet) (Input data) 12 V DC ... 15 V DC (constant capacity)
Conductor cross section AWG max. (Connection data, input) 14
Conductor cross section AWG min. (Connection data, input) 24
Standard - Safe isolation (Connection data for signaling) IEC 61558-2-16
Conductor cross section AWG max. (Connection data, output) 14
Conductor cross section AWG min. (Connection data, output) 24
Conductor cross section solid max. (Connection data, input) 2.5 mm²
Conductor cross section solid min. (Connection data, input) 0.2 mm²
Max. permissible relative humidity (operation) (Dimensions) ≤ 95 % (at 25 °C, non-condensing)
Maximum power dissipation in no-load condition (Input data) < 0.4 W (230 V AC)
Conductor cross section solid max. (Connection data, output) 2.5 mm²
Conductor cross section solid min. (Connection data, output) 0.2 mm²
Recommended breaker for input protection (Ambient conditions) 6 A ... 16 A (Characteristic B, C or comparable)
Conductor cross section flexible max. (Connection data, input) 2.5 mm²
Conductor cross section flexible min. (Connection data, input) 0.2 mm²
Conductor cross section flexible max. (Connection data, output) 2.5 mm²
Conductor cross section flexible min. (Connection data, output) 0.2 mm²
Protection against overvoltage at the output (OVP) (Input data) ≤ 18 V DC
Standard - Safety of transformers (Connection data for signaling) EN 61558-2-16
Asymmetrical conducted disturbance variables (Conformance/approvals) EN 61000-4-16
Standard – Safety extra-low voltage (Connection data for signaling) IEC 61010-1 (SELV)
Attenuated sinusoidal oscillations (ring wave) (Conformance/approvals) EN 61000-4-12
Standard – Limitation of mains harmonic currents (Connection data for signaling) EN 61000-3-2
Standard - safety for equipment for measurement, control, and laboratory use (Connection data for signaling) IEC 61010-1

Popis produktu

Primary switching power supplies, QUINT POWER, Push-in connection, Rail mounting, input:1phase, output: 12 VDC / 2.5 A
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Technické detaily

Block diagram

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top