Čas služby: pondelok až piatok 9:00-18:00
QUINT-PS-100-240AC/24DC/ 5 - QUINT-PS-100-240AC/24DC/ 5 2938581 PHOENIX CONTACT Power supply unit
Na sklade Horúci produkt

QUINT-PS-100-240AC/24DC/ 5

QUINT-PS-100-240AC/24DC/ 5 2938581 PHOENIX CONTACT Power supply unit

$0.00 USD
3168 na sklade
Kľúčové špecifikácie
: 90 V DC ... 350 V DC
Depth: 125 mm
I/O/S: Level 3 - asymmetrical
Input: 4 kV (level 4 - asymmetrical)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
90 V DC ... 350 V DC
Depth 125 mm
I/O/S Level 3 - asymmetrical
Input 4 kV (level 4 - asymmetrical)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width 55 mm
Height 130 mm
Output 2 kV (Level 3 - asymmetrical)
Signal 1 kV (Level 2 - asymmetrical)
Housing Level 4
Voltage 10 V
Comments Criterion B
Derating 60 °C ... 70 °C (2.5 %/K)
Rise time < 2 ms (UOUT(10 % ... 90 %))
EN 62477-1 III
Efficiency > 89 %
Input fuse 5 A (slow-blow, internal)
Output power 120 W
Typ produktu Power supply
Screw thread M3
UL approvals UL/C-UL Recognized UL 60950-1
Assembly note alignable: horizontally 0 mm, vertically 50 mm
Inrush current < 20 A (typical)
Noise emission EN 55011 (EN 55022)
Output voltage + 24 V DC (Signal)
Product family QUINT POWER
Status display "DC OK" LED green
Frequency range 80 MHz ... 2 GHz
Residual ripple < 10 mVPP(with nominal values)
Type of housing AluNox (AlMg1)
Article revision 21
Discharge in air 15 kV
Housing material Metal
Number of phases 1.00
Protection class I (with PE connection)
Stripping length 7 mm
Connection method Pluggable screw connection
Contact discharge 8 kV
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Mounting position horizontal DIN rail NS 35, EN 60715
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Output description UOUT> 0.9 x UN: High signal
Protective circuit Transient surge protection; Varistor
Types of signaling LED
Current consumption approx. 1.6 A (120 V AC)
Degree of pollution 2
Input voltage range 85 V AC ... 264 V AC
Test field strength 10 V/m
Connection in series yes
Degree of protection IP20
Mains buffering time > 30 ms (120 V AC)
Max. capacitive load unlimited
POWER BOOST (IBoost) 7.5 A
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Shipbuilding approval DNV GL (EMC A)
Standards/regulations EN 61000-4-2
Tightening torque max 0.6 Nm
Typical response time < 1 s
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Connection in parallel yes, for redundancy and increased capacity
Input voltage range AC 85 V AC ... 264 V AC
Input voltage range DC 90 V DC ... 350 V DC
Maximum inrush current ≤ 40 mA
Nominal output voltage 24 V DC ±1 %
Note on status display UOUT< 0.9 x UN: LED flashing
Tightening torque, min 0.5 Nm
Continuous load current ≤ 40 mA
Permissible backup fuse B6 B10 B16
Active current limitation Approx. IBOOST= 7.5 A (for short-circuit)
Maximum switching voltage ≤ 24 V
Nominal power consumption 134 W
Operating voltage display Green LED
Standard - Safe isolation DIN VDE 0100-410
MTBF (IEC 61709, SN 29500) > 500000 h
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Feedback voltage resistance 35 V DC
Nominal input voltage range 100 V AC ... 240 V AC
Nominal output current (IN) 5 A (up to 60 °C)
Standard - Equipment safety GS (tested safety)
Power loss nominal load max. < 14 W
Standard - Electrical safety EN 62368-1
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Inrush current integral (I2t) < 2.5 A2s
Insulation voltage input / PE 3.5 kV AC (type test)
Insulation voltage output / PE 500 V DC (routine test)
Voltage type of supply voltage AC/DC
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Insulation voltage input/output 4 kV AC (type test)
Conductor cross section AWG max. 12
Conductor cross section AWG min. 24
Maximum no-load power dissipation < 2 W
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section, rigid min. 0.2 mm²
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise immunity EN 61000-6-1
Peak switching voltages nominal load < 30 mVPP(20 MHz)
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Standard – Safety extra-low voltage EN 62368-1 (SELV)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Setting range of the output voltage (USet) 22.5 V DC ... 28.5 V DC
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Protection against overvoltage at the output (OVP) ≤ 35 V DC
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 62368-1

Popis produktu

Power supply for 24 V DC/5 A DIN rail, switched in primary, single-phase. For new installations use the following items: 2904600
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top