Čas služby: pondelok až piatok 9:00-18:00
PV-SET 2ST/1000DC-SPD-SD-SC - PV-SET 2ST/1000DC-SPD-SD-SC 2801318 PHOENIX CONTACT Lightning and surge arrester in IP65 housing for protect..
Na sklade Horúci produkt

PV-SET 2ST/1000DC-SPD-SD-SC

PV-SET 2ST/1000DC-SPD-SD-SC 2801318 PHOENIX CONTACT Lightning and surge arrester in IP65 housing for protect..

$0.00 USD
4404 na sklade
Kľúčové špecifikácie
: IP65
Type: Installation housing
Color: light grey RAL 7035
Depth: 122 mm
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
IP65
Type Installation housing
Color light grey RAL 7035
Depth 122 mm
Width 200 mm
Height 200 mm
Cable gland M20
Screw thread M2
Sealing area 5 mm ... 13 mm
Mounting type Surface/Wall mounting
Cover material Polycarbonate, transparent
Impact strength IK08
Horizontal pitch 9 Div.
Housing material Polycarbonate, glass-fiber-reinforced
Protection class II
Response time tA ≤ 25 ns
Stripping length 7 mm
Connection method MC 1,5/3
Tightening torque 0.25 Nm
Ambient conditions A, B
Connector material PA
Switching function PDT, 1-pos.
Direction of action (L+)-PE & (L-)-PE & (L+)-(L-)
Degree of protection IP65
Residual current IPE ≤ 25 µA
Rated load current IL 80 A DC
Standards/regulations IEC 61439-2 2011
IEC test classification PV T1
Conductor cross section AWG 30 ... 14 (UL)
Max. operating current Imax 1.5 A AC (250 V AC)
Open circuit voltage UOCSTC 830 V DC (Solar generator)
Rated insulation voltage Ui 1000 V DC
Residual voltage (L+) - (L-) ≤ 3.5 kV (at In)
Short-circuit current ISCSTC 25 A DC
Standby power consumption PC ≤ 25 mVA
Residual voltage (L+/L-) - PE ≤ 3.5 kV (at 15 kA)
Surge protection fault message optical
Ambient temperature (operation) -20 °C ... 40 °C
Recommended backup fuse maximum Not required
Conductor cross section AWG max. 14
Conductor cross section AWG min. 30
Maximum operating voltage UmaxDC 30 V DC
Maximum operating voltage Umax.AC 250 V AC
Conductor cross section solid max. 1.5 mm²
Conductor cross section solid min. 0.14 mm²
Max. backup fuse with branch wiring Not required
Rated surge voltage resistance Uimp 6 kV
Conductor cross section flexible max. 1.5 mm²
Conductor cross section flexible min. 0.14 mm²
Max. discharge current Imax(8/20) µs 40 kA
Flammability rating according to UL 94 V2 (Gehäuse / Deckel)
Nominal discharge current In(8/20) µs 15 kA
Voltage protection level Up(L+) - (L-) ≤ 3.5 kV
Voltage protection level Up(L+/L-) - PE ≤ 3.5 kV
Standards for cearances and creepage distances EN 50539-11

Popis produktu

More details
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top