Kľúčové špecifikácie
: C2
Note: Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
Type: DIN rail module, two-section, divisible
Depth: 77.5 mm (incl. DIN rail 7.5 mm)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
C2
Note Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
Type DIN rail module, two-section, divisible
Depth 77.5 mm (incl. DIN rail 7.5 mm)
Width 17.7 mm
Height 109.3 mm
Altitude ≤ 4000 m (amsl)
Typ produktu Surge protection for MCR technology
Mounting type DIN rail: 35 mm
Rated current 1000 mA (40 °C)
Product family PLUGTRAB IQ
Open side panel No
Horizontal pitch 1 Div.
Housing material PA 6.6
Pollution degree 2
Connection method Push-in connection
Nominal voltage UN 5 V DC
Dimensional drawing
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Resistance per path 1.2 Ω ±5 %
Degree of protection IP20
Overvoltage category III
Residual current IPE ≤ 2 mA (per path)
IEC test classification C1
Standards/specifications IEC 61643-21
Max. required back-up fuse 1 A (FF)
Conductor cross section AWG 24 ... 12
Input attenuation aE, asym. typ. 0.3 dB (≤ 45 kHz/150 Ω)
Capacity (line-signalground) typ. 7.5 nF
Response time tA(line-earth) ≤ 1 ns
Conductor cross section rigid 0.2 mm² ... 4 mm²
Maximum continuous voltage UC 6 V DC
Pulse reset time (line-earth) ≤ 10 ms
Surge protection fault message Optical, multi-stage
Ambient temperature (operation) -40 °C ... 70 °C
Impulse durability (line-earth) C1 - 1 kV / 500 A
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Operating effective current ICat UC ≤ 2 mA (per path)
Flammability rating according to UL 94 V-0
Ambient temperature (storage/transport) -40 °C ... 85 °C
Voltage protection level Up(line-earth) ≤ 120 V (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs 20 kA
Voltage protection level Upstatic (line-earth) ≤ 30 V (C1 - 1 kV / 500 A)
Nominal discharge current In(8/20) µs (line-ground) 10 kA
Pulse discharge current Iimp(10/350) µs (line-earth) 2.5 kA
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system typ. 300 kHz