Čas služby: pondelok až piatok 9:00-18:00
PT 2XEX(I)-24DC-ST - PT 2XEX(I)-24DC-ST 2838225 PHOENIX CONTACT Surge protection plug
Na sklade Horúci produkt

PT 2XEX(I)-24DC-ST

PT 2XEX(I)-24DC-ST 2838225 PHOENIX CONTACT Surge protection plug

$0.00 USD
4927 na sklade
Kľúčové špecifikácie
GTIN: 4017918182861
Orderkey: 2838225
(General): Ex ia IIIC T135 °C...T85 °C Da
Catalog page: Page 132 (C-4-2017)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4017918182861
Orderkey 2838225
(General) Ex ia IIIC T135 °C...T85 °C Da
Catalog page Page 132 (C-4-2017)
Packing unit 10 pc
ATEX (General)  II 1G Ex ia IIC T4...T6 Ga
IECEx (General) Ex ia IIC T4...T6 Ga
Country of origin DE (Germany)
(Connection data) IEC 60079-26 2006
Custom tariff number 85363010
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Rated current (General) 325 mA (40 °C)
(Conformity / approvals) No hazardous substances above threshold values
Type (Ambient conditions) Male
Color (Ambient conditions) sky blue RAL 5015
Depth (Key Commercial Data) 51.7 mm
Width (Key Commercial Data) 17.5 mm
(Standards and Regulations) -40 °C ... 40 °C (T6)
Height (Key Commercial Data) 44.8 mm
Nominal voltage UN (General) 24 V DC
Residual current IPE (General) ≤ 4 µA
Resistance in series (General) 2.2 Ω ±10 %
Degree of protection (Dimensions) IP20
IEC test classification (General) C1
Screw thread (Protective circuit) M3
Mounting type (Ambient conditions) on base element
China RoHS (Conformity / approvals) Environmentally friendly use period: unlimited = EFUP-e
Input attenuation aE, sym. (General) typ. 0.5 dB (≤ 900 kHz / 50 Ω)
Max. required back-up fuse (General) 315 mA (T)
Weight per Piece (excluding packing) 21.090 g
Housing material (Ambient conditions) PA 6.6
Response time tA(line-line) (General) ≤ 1 ns
Stripping length (Protective circuit) 8 mm
Connection method (Protective circuit) Screw connection (in connection with the base element)
Horizontal pitch (Key Commercial Data) 1 Div.
Response time tA(line-earth) (General) ≤ 100 ns
Tightening torque (Protective circuit) 0.5 Nm
Maximum continuous voltage UC (General) 30 V DC
Direction of action (Ambient conditions) Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Impulse durability (line-line) (General) C1 - 0.5 kV / 250 A
Number of positions (Ambient conditions) 4
Surge protection fault message (General) none
Impulse durability (line-earth) (General) C1 - 1 kV/500 A
Standards/specifications (Connection data) EN 61643-21 A2:2013
Complete module depth (Key Commercial Data) 65.5 mm
Complete module width (Key Commercial Data) 17.7 mm
Residual voltage at In(line-line) (General) ≤ 45 V
Ambient temperature (operation) (Dimensions) -40 °C ... 85 °C
Complete module height (Key Commercial Data) 90 mm
Operating effective current ICat UC (General) ≤ 5 µA
max. input power Pi (Standards and Regulations) 3 W
Conductor cross section AWG (Protective circuit) 24 ... 12
Voltage protection level Up(line-line) (General) ≤ 45 V (C1 - 0.5 kV / 250 A)
Max. input current Ii (Standards and Regulations) 325 mA (T4 / ≤ 80°C)
Max. input voltage Ui (Standards and Regulations) 30 V DC
Voltage protection level Up(line-earth) (General) ≤ 1 kV (C1 - 1 kV/500 A)
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General) 20 kA
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 85 °C
Total discharge current Itotal(10/350) µs (General) 2 kA
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 2.5 mm²
Max. internal inductance Li (Standards and Regulations) 1 µH
Maximum inner capacitance Ci (Standards and Regulations) 1.3 nF
Ambient temperature (operation) (Standards and Regulations) -40 °C ... 80 °C (T4)
Flammability rating according to UL 94 (Ambient conditions) V-0
Alternating current carrying capacity (line-earth) (General) 10 A - 1 s
Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General) typ. 4.5 MHz
Nominal discharge current In(8/20) µs (line-line) (General) 10 kA
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) typ. 1.6 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ohm system (General) typ. 400 kHz
Maximum inner time factor (Ri/Li) (Standards and Regulations) ≤ 0.2 µs
Nominal discharge current In(8/20) µs (line-earth) (General) 10 kA
Nominal pulse current Ian (10/1000) µs (line-line) (General) 30 A
Residual voltage with Ian (10/1000) µs (line-line) (General) ≤ 50 V
Pulse discharge current Iimp(10/350) µs (line-line) (General) 1 kA
Pulse discharge current Iimp(10/350) µs (line-earth) (General) 2 kA (in total)
Output voltage limitation at 1 kV/µs (line-line) spike (General) ≤ 45 V
Output voltage limitation at 1 kV/µs (line-earth) spike (General) ≤ 1 kV
Output voltage limitation at 1 kV/µs (line-line) static (General) ≤ 45 V
Max. discharge current Imax(8/20) µs maximum (line-line) (General) 10 kA
Output voltage limitation at 1 kV/µs (line-earth) static (General) ≤ 1 kV
Max. discharge current Imax(8/20) µs maximum (line-earth) (General) 20 kA (in total)
Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) From SW rev. 1.00

Popis produktu

PT plug-in protection protection circuit for two 2-conductor Ex i signal circuits driven free of ground potential. Nominal voltage: 24 V DC, suitable for HART.
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top