Čas služby: pondelok až piatok 9:00-18:00
PT 2X1-VF-230AC-ST - PT 2X1-VF-230AC-ST 2921365 PHOENIX CONTACT Surge protection plug
Na sklade Horúci produkt

PT 2X1-VF-230AC-ST

PT 2X1-VF-230AC-ST 2921365 PHOENIX CONTACT Surge protection plug

$0.00 USD
4879 na sklade
Kľúčové špecifikácie
: C2
Note: 2002
Type: Male
Color: black (RAL 9005)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
C2
Note 2002
Type Male
Color black (RAL 9005)
Depth 51.7 mm
Width 17.5 mm
Height 44.8 mm
Altitude ≤ 2000 m (amsl)
Typ produktu Surge protection for MCR technology
Screw thread M3
Mounting type on base element
Rated current 6 A
Product family PLUGTRAB PT
Open side panel No
Article revision 08
Horizontal pitch 1 Div.
Housing material PA 6.6
Response time tA ≤ 100 ns
Connection method Screw connection (in connection with the base element)
Tightening torque 0.8 Nm
Nominal voltage UN 230 V AC
Switching function N/C contact
Dimensional drawing
Direction of action Line-Line & Line-Earth Ground
Number of positions 2
Resistance per path 0 Ω
Capacity (Core-Core) typ. 1.5 pF
Degree of protection IP20
Residual current IPE ≤ 2 µA (at UN)
Capacity (Core-Earth) typ. 3 pF
Complete module depth 65.5 mm
Complete module width 17.7 mm
Complete module height 90 mm
IEC test classification C1
Standards/specifications EN 61643-21
Max. required back-up fuse 6 A (gL/gG)
Conductor cross section AWG 24 ... 12
Conductor cross section rigid 0.2 mm² ... 4 mm²
Max. energy absorption (2 ms) 150 J
Maximum continuous voltage UC 250 V AC
Surge protection fault message none
Ambient temperature (operation) -40 °C ... 80 °C
Impulse durability (line-earth) C2 - 4 kV / 2 kA
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Operating effective current ICat UC ≤ 2 µA
Max. discharge current Imax(8/20) µs 8 kA
Flammability rating according to UL 94 V-0
Nominal discharge current In(8/20) µs 3 kA
Voltage protection level Up(line-line) ≤ 2.5 kV (C2 - 4 kV / 2 kA)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Voltage protection level Up(line-earth) ≤ 1.1 kV (C1 - 500 A)
Residual voltage at In(conductor-ground) ≤ 1 kV
Pulse discharge current Iimp(10/350) µs 500 A
Total discharge current Itotal(8/20) µs 8 kA
Residual voltage at In(conductor-conductor) ≤ 2 kV
Total discharge current Itotal(10/350) µs 1 kA
Residual voltage with Ian (10/1000) µs (line-line) ≤ 1.4 kV
Nominal pulse current Ian (10/1000) µs (line-earth) 100 A
Residual voltage with Ian (10/1000) µs (line-earth) ≤ 700 V
Output voltage limitation at 1 kV/µs (line-earth) static ≤ 1.4 kV

Popis produktu

Plug-in protection with leakage current-proof protection circuit for two signals without earth potential. Series circuit consisting of varistor and a gas-filled surge arrester between the signal and g
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top