Čas služby: pondelok až piatok 9:00-18:00
PSR-SCP-24UC/THC4/2X1/1X2 - PSR-SCP- 24UC/THC4/2X1/1X2 2963721 PHOENIX CONTACT Safety relays
Na sklade Horúci produkt

PSR-SCP-24UC/THC4/2X1/1X2

PSR-SCP- 24UC/THC4/2X1/1X2 2963721 PHOENIX CONTACT Safety relays

$0.00 USD
4393 na sklade
Kľúčové špecifikácie
GTIN: 4017918818692
Orderkey: 2963721
Catalog page: Page 262 (C-6-2017)
Depth (Note): 114.5 mm
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4017918818692
Orderkey 2963721
Catalog page Page 262 (C-6-2017)
Depth (Note) 114.5 mm
Packing unit 1 pc
Width (Note) 22.5 mm
(Input data) 6 A gL/gG NEOZED (N/C contact)
Height (Note) 99 mm
(Output data) IP54
Country of origin DE (Germany)
pluggable (General) Yes
Custom tariff number 85371098
(Ambient conditions) Surge protection Suppressor diode
Screw thread (General) M3
Net weight (Output data) 193.3 g
Output fuse (Input data) 10 A gL/gG NEOZED (N/O contact)
Relay type (Output data) Electromechanical relay with forcibly guided contacts in accordance with EN 50205
Contact type (Input data) 2 enabling current paths
Category (Connection data) 4
Stripping length (General) 7 mm
Connection method (General) Screw connection
Housing color (Output data) yellow
Mounting type (Output data) DIN rail mounting
(Standards and Regulations) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Type class (Connection data) IIIC
Contact material (Input data) AgSnO2, + 0.2 µm Au
Designation (Connection data) EN 62061
Maximum altitude (Dimensions) max. 2000 m (Above sea level)
Mounting position (Output data) any
Stop category (Connection data) 0
Degree of protection (Output data) IP20
Recovery time (Ambient conditions) 1 s
Maximum inrush current (Input data) 6 A
Status display (Ambient conditions) Green LED
Inrush current, minimum (Input data) 25 mA
Mechanical service life (Input data) approx. 107cycles
Nominal operating mode (Output data) 100% operating factor
Switching capacity min. (Input data) 0.4 W
Weight per Piece (excluding packing) 193.300 g
China RoHS (Standards and Regulations) Environmentally Friendly Use Period = 50
Maximum switching voltage (Input data) 250 V AC/DC
Minimum switching voltage (Input data) 15 V AC/DC
Protective circuit (Ambient conditions) Fuse PTC resistor
Input voltage range (Ambient conditions) 20.4 V AC/DC ... 26.4 V AC/DC
Limiting continuous current (Input data) 6 A (N/O contact)
Performance level (PL) (Connection data) e
Typical release time (Ambient conditions) 20 ms
Concurrence input 1/2 (Ambient conditions) < 0.5 s
Conductor cross section AWG max. (General) 12
Conductor cross section AWG min. (General) 24
Shock (Safety-related characteristic data) 15g
Typical response time (Ambient conditions) 50 ms
Ambient temperature (operation) (Dimensions) -20 °C ... 55 °C
Conductor cross section solid max. (General) 2.5 mm²
Conductor cross section solid min. (General) 0.2 mm²
Nominal input voltage UN (Ambient conditions) 24 V AC/DC
Utilization restriction (Key Commercial Data) EMC: class A product, see manufacturer's declaration in the download area
Operating voltage display (Ambient conditions) Green LED
Safety Integrity Level (SIL) (Connection data) 3
Switching capacity (360/h cycles) (Input data) 4 A (24 V DC)
Conductor cross section flexible max. (General) 2.5 mm²
Conductor cross section flexible min. (General) 0.2 mm²
Designation (Safety-related characteristic data) Air clearances and creepage distances between the power circuits
Typical input current at UN (Ambient conditions) 125 mA AC
Interrupting rating (ohmic load) max. (Input data) 144 W (24 V DC, τ = 0 ms)
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 70 °C
Degree of pollution (Safety-related characteristic data) 2
Maximum interrupting rating (inductive load) (Input data) 42 W (24 V DC, τ = 40 ms)
Min. degree of protection of inst. location (Output data) IP54
Overvoltage category (Safety-related characteristic data) III
Max. permissible humidity (storage/transport) (Dimensions) 75 % (on average, 85% infrequently, non-condensing)
Standards/regulations (Safety-related characteristic data) DIN EN 50178/VDE 0160
Vibration (operation) (Safety-related characteristic data) 10 Hz ... 150 Hz, 2g
Input voltage range in reference to UN (Ambient conditions) 0.85 ... 1.1
Max. permissible relative humidity (operation) (Dimensions) 75 % (on average, 85% infrequently, non-condensing)
Rated insulation voltage (Safety-related characteristic data) 250 V
Safety Integrity Level Claim Limit (SIL CL) (Connection data) 3
Voltage at input/start and feedback circuit (Ambient conditions) approx. 24 V DC
Rated surge voltage/insulation (Safety-related characteristic data) 6 kV / Safe isolation, increased insulation

Popis produktu

Safety relay for two-hand control systems according to ISO 13851 type IIIC up to SIL 3 or cat. 4, PL e according to EN ISO 13849, synchronous transmission monitoring < 0.5 s, 2 NO contacts, 1 NC conta
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top