Kľúčové špecifikácie
: 250 V
Plug: Yes
Crash: 35%
Depth: 114.5 mm
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
250 V
Plug Yes
Crash 35%
Depth 114.5 mm
Width 35 mm
Height 99 mm
Marked CE Compliance
category 4 (in combination with suitable evaluation device)
Relay Type Electromechanical relay with forced conduction contacts according to IEC/EN 61810-3
Output fuse 10 A gL/gG
application Expansion module
Product Type Safety Relay
Screw thread M3
Fixing height ≤ 2000 m (via NN)
Input current min. 10 mA
Recovery Time < 1 sec
Stop Category 0
Product Family PSRclassic
Shell material Polyamide
Connection type Screw connection
AWG Wire Section 24 ... 12
Contact Material AgSnO2
Protection Index IP20
Type of mounting Rail mounting
Number of Entries 2
Number of outputs 5
Switching voltage min. 10 V
Tightening torque 0.5 Nm ... 0.6 Nm
Current absorption Typ. 39 mA
Protection Circuit Suppressor diode
Ticket Description Safety-oriented
Square. Current Sum 72 A2(observe derating)
Switching frequency max. 1 Hz
Vibration (service) 10 Hz ... 150 Hz, amplitude 0.15 mm, 2g
Min. switching power min. 100 mW
Typical Opening Time < 20 ms (with Us/with excitation via A11/A12)
Position for mounting Vertical or horizontal
Constant Current Limit 6 A (observe derating)
Contact Switching Type 5 Release Intensity Circuits
Nominal Operating Type Working time 100%
Performance Level (PL) e (in combination with appropriate evaluation device)
Mechanical service life approx.107Status Change Periodicities
Rigid conductor section 0.2 mm² ... 2.5 mm²
Standards/Specifications EN 60947-1
Description of the output each 2 NO in series, safety-oriented, potential-free
Installation instructions Observe derating
Length to be de-insulated 7 mm
Operating voltage display 2 x Green LEDs
Sizing Insulation Voltage 250 V
Flexible conductor section 0.2 mm² ... 2.5 mm²
Safety Integrity Level (SIL) 3 (in combination with suitable evaluation device)
Ambient Temperature (Service) -20 °C ... 55 °C (observe derating)
Input Voltage Range Signal "1" 19.2 V ... 26.4 V DC
Typical Excitation Time with Us < 25 ms (with Us/with excitation via A11/A12)
Sizing/Insulation Transient Voltage See the chapter Coordination of insulations
Total permissible line resistance max. 50 Ω
Ambient Temperature (Storage/Transport) -40 °C ... 70 °C
Max. permissible air humidity (service) 75% (On average, occasionally 85%, non-condensing)
Breaking capacity according to IEC 60947-5-1 3 A (AC15)
Maximum Dissipated Power with Nominal Condition 16.7 W (Us= 26.4 V, IL² = 72 A², PTotal Max= 2.3 W + 14.4 W)
Max. permissible air humidity (storage/transport) 75% (On average, occasionally 85%, non-condensing)
Minimum degree of protection of the installation site IP54

Popis produktu

More details
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu