Čas služby: pondelok až piatok 9:00-18:00
PSR-MC38-2NO-1DO-24DC-PI - PSR-MC38-2NO-1DO-24DC-PI 1009832 PHOENIX CONTACT Safety relay for emergency stop, safety doors and light gri..
Na sklade Horúci produkt

PSR-MC38-2NO-1DO-24DC-PI

PSR-MC38-2NO-1DO-24DC-PI 1009832 PHOENIX CONTACT Safety relay for emergency stop, safety doors and light gri..

$0.00 USD
3404 na sklade
Kľúčové špecifikácie
GTIN: 4055626482712
Orderkey: 1009832
(Drawings):
Catalog page: Page 223 (C-6-2019)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4055626482712
Orderkey 1009832
(Drawings)
Catalog page Page 223 (C-6-2019)
Depth (Note) 114.5 mm
Packing unit 1 pc
Width (Note) 22.5 mm
Height (Note) 117.5 mm
(Power supply) typ. 34 µA (Typically with USat S35)
(Alarm outputs) 60 ms (when controlled via A1)
(Digital inputs) 4 A gL/gG (for low-demand applications)
Country of origin DE (Germany)
ETIM 5.0 (eCl@ss) EC001449
ETIM 6.0 (eCl@ss) EC001449
ETIM 7.0 (eCl@ss) EC001449
Net weight (Times) 169.38 g
Relay type (Times) Electromechanical relay with forcibly guided contacts in accordance with EN 50205
pluggable (General) no
Custom tariff number 85371098
Housing color (Times) yellow
Mounting type (Times) DIN rail mounting
Status display (Times) 4 x green LEDs
Housing material (Times) PBT
Input name (Power supply) Start circuit
Mounting position (Times) vertical or horizontal
Category (Connection data) 4 (5 A DC13; 5 A AC15; 8760 switching cycles/year)
Filter time (Power supply) 2 ms (At S10, S12, S13; test pulse width of low test pulses)
Stripping length (General) 10 mm
Connection method (General) Push-in connection
Degree of protection (Times) IP20
Output fuse (Digital inputs) 10 A gL/gG
Output name (Digital inputs) Enabling current path
Restart time (Alarm outputs) < 1 s (Boot time)
eCl@ss 8.0 (Classifications) 27371819
eCl@ss 9.0 (Classifications) 27371819
Assembly instructions (Times) See derating curve
Contact type (Digital inputs) 2 enabling current paths
Designation (Connection data) EN 62061
Inrush current (Power supply) < 60 mA (Typically with USat Y1, Δt = 150 ms)
Maximum altitude (Dimensions) ≤ 2000 m (Above sea level)
Recovery time (Alarm outputs) < 500 ms
Nominal operating mode (Times) 100% operating factor
Inrush current (Digital inputs) min. 10 mA
Number of inputs (Power supply) 4
Stop category (Connection data) 0
Designation (Ambient conditions) A1/A2
Filter time (Ambient conditions) 20 ms (at A1 in the event of voltage dips at Us)
Contact material (Digital inputs) AgSnO2
Operating voltage display (Times) 1 x green LED
Current consumption (Power supply) typ. 10 mA (Typically with USat Y1)
Number of outputs (Digital inputs) 2 (undelayed)
Sq. Total current (Digital inputs) 72 A2(observe derating)
Switching voltage (Digital inputs) min. 10 V AC/DC
Utilization restriction (Drawings) EMC: class A product, see manufacturer's declaration in the download area
Inrush current (Ambient conditions) < 4 A (Δt = 3 ms at Us)
Output description (Digital inputs) safety-related N/O contacts
Switching capacity (Digital inputs) min. 100 mW
Concurrence input 1/2 (Power supply)
Switching frequency (Digital inputs) max. 0.5 Hz
Weight per Piece (excluding packing) 180.000 g
(Safety-related characteristic data) 250 V
REACh SVHC (Standards and Regulations) Lead 7439-92-1
(Relay outputs: enabling current path) non-safety-related
Description of the input (Power supply) non-safety-related
Protective circuit (Ambient conditions) Serial protection against polarity reversal Suppressor diode
Mechanical service life (Digital inputs) 10x 106cycles
No preview imageBlock diagram (Drawings)
Performance level (PL) (Connection data) e
Typical pickup time at US (Alarm outputs) 200 ms (when controlled via A1)
Conductor cross section AWG max. (General) 14
Conductor cross section AWG min. (General) 24
Shock (Safety-related characteristic data) 15g
Typical release time at US (Alarm outputs) 25 ms (when actuation is via the sensor circuit)
Protective circuit/component (Power supply) Suppressor diode
Typical response time at US (Alarm outputs) 200 ms (automatic start)
Ambient temperature (operation) (Dimensions) -20 °C ... 55 °C (observe derating)
Conductor cross section solid max. (General) 2.5 mm²
Conductor cross section solid min. (General) 0.2 mm²
Limiting continuous current (Digital inputs) 6 A
Power consumption at US (Ambient conditions) typ. 1.8 W
Input voltage range "1" signal (Power supply) 20.4 V DC ... 26.4 V DC
Current (Relay outputs: enabling current path) max. 100 mA
Safety Integrity Level (SIL) (Connection data) 3
Voltage (Relay outputs: enabling current path) approx. 23.9 V DC (Us- 0.1 V)
Conductor cross section flexible max. (General) 2.5 mm²
Conductor cross section flexible min. (General) 0.2 mm²
Conformance (Safety-related characteristic data) CE-compliant
Designation (Safety-related characteristic data) Air clearances and creepage distances between the power circuits
Designation (Relay outputs: enabling current path) Y30
Min. degree of protection of inst. location (Times) IP54
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 70 °C
Rated control supply current IS (Ambient conditions) typ. 75 mA
Degree of pollution (Safety-related characteristic data) 2
Number of outputs (Relay outputs: enabling current path) 1
Output description (Relay outputs: enabling current path) PNP
Overvoltage category (Safety-related characteristic data) III
Max. permissible humidity (storage/transport) (Dimensions) 75 % (on average, 85% infrequently, non-condensing)
Standards/regulations (Safety-related characteristic data) DIN EN 50178
Vibration (operation) (Safety-related characteristic data) 10 Hz ... 150 Hz, 2g
Max. permissible relative humidity (operation) (Dimensions) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance (Power supply) 50 Ω
Rated control circuit supply voltage US (Ambient conditions) 24 V DC -15 % / +10 % (provide external protection)
Maximum inrush current (Relay outputs: enabling current path) 500 mA (Δt = 1 ms at Us)
Rated insulation voltage (Safety-related characteristic data) 250 V
Safety Integrity Level Claim Limit (SIL CL) (Connection data) 3
Switching capacity according to IEC 60947-5-1 (Digital inputs) 5 A (24 V (DC13))
Protective circuit/component (Relay outputs: enabling current path) Suppressor diode

Popis produktu

Safety relay for emergency stop, protection doors and light barrier up to SIL 3, cat. 4, PL e, 1 or 2 channel operation, automatic or manual, monitored start, 2 trip circuits, 1 message output, TBUS i
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Technické detaily

Block diagram

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu