Čas služby: pondelok až piatok 9:00-18:00
PSR-MC20-3NO-1DO-24DC-SP - PSR-MC20-3NO-1DO-24DC-SP 2700467 PHOENIX CONTACT Safety relays
Na sklade Horúci produkt

PSR-MC20-3NO-1DO-24DC-SP

PSR-MC20-3NO-1DO-24DC-SP 2700467 PHOENIX CONTACT Safety relays

$0.00 USD
3479 na sklade
Kľúčové špecifikácie
GTIN: 4046356912754
Orderkey: 2700467
Catalog page: Page 252 (C-6-2017)
Depth (Note): 114.5 mm
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4046356912754
Orderkey 2700467
Catalog page Page 252 (C-6-2017)
Depth (Note) 114.5 mm
Packing unit 1 pc
Width (Note) 12.5 mm
Height (Note) 116.6 mm
(Power supply) Test pulse rate = 5 x Test pulse width
(Alarm outputs) < 175 ms (manual, monitored start)
(Digital inputs) 4 A gL/gG (for low-demand applications)
Country of origin DE (Germany)
Net weight (Times) 140.4 g
Relay type (Times) Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205)
pluggable (General) Yes
Custom tariff number 85371098
(Ambient conditions) Protection against polarity reversal for rated control circuit supply voltage
Housing color (Times) yellow
Mounting type (Times) DIN rail mounting
Status display (Times) 3 x green LED
Housing material (Times) PBT
Mounting position (Times) vertical or horizontal
Category (Connection data) 1 (up to Cat. 4 depending on the application)
Filter time (Power supply) max. 1.5 ms (at S12; test pulse width)
Stripping length (General) 8 mm
Connection method (General) Spring-cage connection
(Standards and Regulations) No hazardous substances above threshold values
Degree of protection (Times) IP20
Output fuse (Digital inputs) 6 A gL/gG (N/O contact)
Output name (Digital inputs) Enabling current path
Assembly instructions (Times) See derating curve
Contact type (Digital inputs) 3 enabling current paths
Designation (Connection data) EN 62061
Inrush current (Power supply) < 21 mA (with Us/Ixto S12)
Maximum altitude (Dimensions) ≤ 2000 m (Above sea level)
Recovery time (Alarm outputs) < 500 ms
Nominal operating mode (Times) 100% operating factor
Inrush current (Digital inputs) min. 3 mA
Stop category (Connection data) 0
Filter time (Ambient conditions) 1 ms (at A1 in the event of voltage dips at Us)
Contact material (Digital inputs) AgSnO2
Operating voltage display (Times) 1 x green LED
Current consumption (Power supply) < 5 mA (with Us/Ixto S12)
Number of outputs (Digital inputs) 3 (undelayed)
Sq. Total current (Digital inputs) 48 A2(observe derating)
Switching voltage (Digital inputs) min. 12 V AC/DC
Inrush current (Ambient conditions) 5 A (Δt = 200 µs at Us)
Output description (Digital inputs) safety-related N/O contacts
Switching capacity (Digital inputs) min. 60 mW
Switching frequency (Digital inputs) 0.5 Hz
Weight per Piece (excluding packing) 140.400 g
(Safety-related characteristic data) 250 V AC
China RoHS (Standards and Regulations) Environmentally friendly use period: unlimited = EFUP-e
REACh SVHC (Standards and Regulations) Lead 7439-92-1
Protective circuit (Ambient conditions) Surge protection Suppressor diode
Mechanical service life (Digital inputs) 10x 106cycles
Performance level (PL) (Connection data) c (up to PL e depending on the application)
Typical pickup time at US (Alarm outputs) < 250 ms (when controlled via A1)
Conductor cross section AWG max. (General) 16
Conductor cross section AWG min. (General) 24
Shock (Safety-related characteristic data) 15g
Typical release time at US (Alarm outputs) < 20 ms (when controlled via A1 or S12)
Typical response time at US (Alarm outputs) < 175 ms (automatic start)
Ambient temperature (operation) (Dimensions) -40 °C ... 55 °C (observe derating)
Conductor cross section solid max. (General) 1.5 mm²
Conductor cross section solid min. (General) 0.2 mm²
Limiting continuous current (Digital inputs) 6 A (observe derating)
Power consumption at US (Ambient conditions) typ. 1.92 W
Input current range "0" signal (Power supply) 0 mA ... 2 mA (for safe Off; at S12)
Input voltage range "0" signal (Power supply) 0 V DC ... 5 V DC (for safe Off; at S12)
Utilization restriction (Key Commercial Data) 1
Current (Relay outputs: enabling current path) max. 100 mA
Safety Integrity Level (SIL) (Connection data) 1 (up to SIL 3 depending on the application)
Voltage (Relay outputs: enabling current path) 22 V DC (Us- 2 V)
Conductor cross section flexible max. (General) 1.5 mm²
Conductor cross section flexible min. (General) 0.2 mm²
Designation (Safety-related characteristic data) Air clearances and creepage distances between the power circuits
Min. degree of protection of inst. location (Times) IP54
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 85 °C
Rated control supply current IS (Ambient conditions) typ. 80 mA
Degree of pollution (Safety-related characteristic data) 2
Number of outputs (Relay outputs: enabling current path) 1 (digital, PNP)
Output description (Relay outputs: enabling current path) non-safety-related
Overvoltage category (Safety-related characteristic data) III
Max. permissible humidity (storage/transport) (Dimensions) 75 % (on average, 85% infrequently, non-condensing)
Standards/regulations (Safety-related characteristic data) DIN EN 50178
Vibration (operation) (Safety-related characteristic data) 10 Hz ... 150 Hz, 2g
Voltage at input/start and feedback circuit (Power supply) 24 V DC -15 % / +10 %
Max. permissible relative humidity (operation) (Dimensions) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance (Power supply) 150 Ω
Rated control circuit supply voltage US (Ambient conditions) 24 V DC -15 % / +10 %
Maximum inrush current (Relay outputs: enabling current path) 500 mA (Δt = 1 ms at Us)
Rated insulation voltage (Safety-related characteristic data) 250 V AC
Safety Integrity Level Claim Limit (SIL CL) (Connection data) 1 (up to SILCL 3 depending on the application)
Short-circuit protection (Relay outputs: enabling current path) no
Rated surge voltage/insulation (Safety-related characteristic data) Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24) and enabling current path (33/34)Basic insulation 4 kV between all current paths and housing

Popis produktu

Safety relay for emergency stop/safety doors up to SIL 1, cat. 1, PL c, depending on the application up to SIL 3, cat. 4, PL e, 1-channel service, automatic or manual start, 3 trip circuits, US = 24 V
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu