Čas služby: pondelok až piatok 9:00-18:00
MT-RS485 - MT-RS485 2762265 PHOENIX CONTACT Surge protection device
Na sklade Horúci produkt

MT-RS485

MT-RS485 2762265 PHOENIX CONTACT Surge protection device

$0.00 USD
4860 na sklade
Kľúčové špecifikácie
GTIN: 4017918064945
Orderkey: 2762265
(General): 0.1 dB (up to 10 kHz 600 Ω system)
Catalog page: Page 100 (TT-2002)
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4017918064945
Orderkey 2762265
(General) 0.1 dB (up to 10 kHz 600 Ω system)
Catalog page Page 100 (TT-2002)
Packing unit 5 pc
Country of origin DE (Germany)
Custom tariff number 85363010
Rated current (General) 450 mA (25 °C)
Type (Ambient conditions) DIN rail module, one-piece
Color (Ambient conditions) black
Depth (Key Commercial Data) 54.9 mm
Width (Key Commercial Data) 47.6 mm
Height (Key Commercial Data) 77.5 mm
Resistance in series (General) 4.4 Ω
VDE requirement class (General) C2
Degree of protection (Dimensions) IP20
IEC test classification (General) C2
Screw thread (Protective circuit) M3
Mounting type (Ambient conditions) DIN rail: 35 mm
Input attenuation aE, sym. (General)
Weight per Piece (excluding packing) 101.950 g
Input attenuation aE, asym. (General) 0.8 dB (up to 0.1 MHz 50 Ω system)
Response time tA(line-line) (General) 1 ns
Stripping length (Protective circuit) 8 mm
Connection method (Protective circuit) Screw connection
REACh SVHC (Standards and Regulations) Lead 7439-92-1
Response time tA(line-earth) (General) ≤ 100 ns
Tightening torque (Protective circuit) 0.5 Nm ... 0.6 Nm
Maximum continuous voltage UC (General) 12 V DC
Standards/regulations (Connection data) IEC 61643-21
Direction of action (Ambient conditions) Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Surge protection fault message (General) none
Connection method IN (Protective circuit) Screw terminal blocks
Connection method OUT (Protective circuit) Screw terminal blocks
Residual voltage at In(line-line) (General) ≤ 19 V
Ambient temperature (operation) (Dimensions) -40 °C ... 60 °C
Operating effective current ICat UC (General) ≤ 10 µA
Response time tA (line-signalground) (General) ≤ 1 ns
Conductor cross section AWG (Protective circuit) 24 ... 12
Voltage protection level Up(line-line) (General) ≤ 22 V
Voltage protection level Up(line-earth) (General) ≤ 600 V
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Pulse discharge current Iimp(10/350) µs (General) 500 A
Residual voltage at In(line-signalground) (General) ≤ 19 V
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 2.5 mm²
Voltage protection level Up(line-signalground) (General) ≤ 22 V
Nominal discharge current In(8/20) µs (line-line) (General) 10 kA
Nominal discharge current In(8/20) µs (line-earth) (General) 10 kA
Output voltage limitation at 1 kV/µs (line-line) spike (General) ≤ 22 V
Output voltage limitation at 1 kV/µs (line-earth) spike (General) ≤ 600 V
Output voltage limitation at 1 kV/µs (line-line) static (General) ≤ 22 V
Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system (General) 1.3 MHz
Output voltage limitation at 1 kV/µs (line-earth) static (General) ≤ 600 V
Cut-off frequency fg (3 dB), asym. (GND) in 600 Ohm system (General) 130 kHz
Output voltage limitation at 1 kV/µs (line-signalground) static (General) ≤ 22 V

Popis produktu

Rail mounting module with coarse and fine surge protection for RS-485 interface, for mounting on NS 35/7.5, housing width: 50 mm
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu