Čas služby: pondelok až piatok 9:00-18:00
FLT-SEC-T1+T2-2IT-350/25-FM - FLT-SEC-T1+T2-2IT-350/25-FM 1044388 PHOENIX CONTACT Type 1+2 protective device combination
Na sklade Horúci produkt

FLT-SEC-T1+T2-2IT-350/25-FM

FLT-SEC-T1+T2-2IT-350/25-FM 1044388 PHOENIX CONTACT Type 1+2 protective device combination

$0.00 USD
4035 na sklade
Kľúčové špecifikácie
GTIN: 4055626620862
Note: Made to Order (non-returnable)
Orderkey: 1044388
Packing unit: 1 pc
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
GTIN 4055626620862
Note Made to Order (non-returnable)
Orderkey 1044388
Packing unit 1 pc
Country of origin DE (Germany)
(Connection data) EN 61643-11 2012
Custom tariff number 85363030
(Ambient conditions) PBT-FR
(Protective circuit) 1 A DC (30 V DC)
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions) DIN rail module, two-section, divisible
(Additional descriptions) ≤ 0.9 kV (at 3 kA / L2-PE)
Color (Ambient conditions) light gray RAL 7035
Depth (Key Commercial Data) 74.5 mm
Width (Key Commercial Data) 71.2 mm
EN type (Ambient conditions) T1 + T2
Height (Key Commercial Data) 95.2 mm
Shock (operation) (Dimensions) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Degree of protection (Dimensions) IP20 (only when all terminal points are used)
Screw thread (Protective circuit) M2
Mounting type (Ambient conditions) DIN rail: 35 mm
Vibration (operation) (Dimensions) 5g (5 - 500 Hz/2.5 h/X, Y, Z)
Weight per Piece (excluding packing) 633.600 g
Housing material (Ambient conditions) PA 6.6-FR 20% GF
Stripping length (Protective circuit) 7 mm
Connection method (Protective circuit) Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data) 4 Div.
Operating current (Protective circuit) 10 mA AC ... 1 A AC
Operating voltage (Protective circuit) 12 V AC ... 250 V AC
REACh SVHC (Standards and Regulations) Lead 7439-92-1
Tightening torque (Protective circuit) 0.25 Nm
Mode of protection (Ambient conditions) L-PE
Standards/regulations (Connection data) IEC 61643-11 2011
Switching function (Protective circuit) PDT contact
Degree of pollution (Ambient conditions) 2
Screw thread (Indicator/remote signaling) M5
Response time tA (Additional descriptions) ≤ 25 ns
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) IT
IEC test classification (Ambient conditions) I + II
Nominal voltage UN (Additional descriptions) 240 V AC (IT)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Stripping length (Indicator/remote signaling) 18 mm
Connection method (Indicator/remote signaling) Fork-type cable lug
Nominal frequency fN (Additional descriptions) 50 Hz (60 Hz)
Residual current IPE (Additional descriptions) ≤ 0.5 mA
Tightening torque (Indicator/remote signaling) 4.5 Nm
Rated load current IL (Additional descriptions) 125 A (< 55 °C)
Conductor cross section AWG (Protective circuit) 28 ... 16
Conductor cross section solid (Protective circuit) 0.14 mm² ... 1.5 mm²
TOV behavior at UT(L-PE) (Additional descriptions) 415 V AC (5 s / withstand mode)
Surge protection fault message (Ambient conditions) Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Residual voltage Ures(L-L) (Additional descriptions) ≤ 1.5 kV (at In/ L1-L2)
Conductor cross section flexible (Protective circuit) 0.14 mm² ... 1.5 mm²
Residual voltage Ures(L-PE) (Additional descriptions) ≤ 2.8 kV (at In/ L1-PE)
Conductor cross section AWG (Indicator/remote signaling) 13 ... 2
Conductor cross section solid (Indicator/remote signaling) 2.5 mm² ... 35 mm²
Voltage protection level Up(L-L) (Additional descriptions) ≤ 1.5 kV (L1-L2)
Flammability rating according to UL 94 (Ambient conditions) V-0
Voltage protection level Up(L-PE) (Additional descriptions) ≤ 2.8 kV (L1-PE)
Short-circuit current rating ISCCR (Additional descriptions) 25 kA (264 V AC)
Conductor cross section flexible (Indicator/remote signaling) 1.5 mm² ... 16 mm²
Max. backup fuse with branch wiring (Additional descriptions) 315 A (gG)
Nominal discharge current In(8/20) µs (Additional descriptions) 25 kA
Follow current interrupt rating Ifi(L-PE) (Additional descriptions) 25 kA (264 V AC)
Max. backup fuse with V-type through wiring (Additional descriptions) 125 A (gG)
Maximum continuous operating voltage UC(L-PE) (Additional descriptions) 350 V AC
Impulse discharge current (10/350) µs, charge (Additional descriptions) 12.5 As
Impulse discharge current (10/350) µs, peak value limp (Additional descriptions) 25 kA
Impulse discharge current (10/350) µs, specific energy (Additional descriptions) 160 kJ/Ω

Popis produktu

Combination of pluggable lightning and surge arresters, according to type 1+2/class I+II, for two-phase power supply networks with isolated operation (L1, L2, PE).
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top