Kľúčové špecifikácie
(): 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
GTIN: 4046356170598
FLA (): 6.5 A (500 V AC)
SCCR (): 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
Informácie o dodávateľovi
Produkty: 0
Zvyčajne sa odosiela do 2-3 pracovných dní
Zaručená kvalita
Rýchle doručenie
Technická podpora

Technické špecifikácie

Parameter Hodnota
() 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
GTIN 4046356170598
FLA () 6.5 A (500 V AC)
SCCR () 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
Orderkey 2297060
(UL data) Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Catalog page Page 19 (C-7-2013)
Packing unit 1 pc
(Input data) 6.5 A (AC-53a)
(Device supply) 85 V AC (“1” signal)
Category code () NLDX
Torque (General) 0.5 Nm ... 0.6 Nm
Country of origin DE (Germany)
Mains frequency () 40/100 Hz
Custom tariff number 85371098
Insulation (UL data) Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Designation (UL data) Isolation characteristics between the control input and control supply voltage to auxiliary circuit
Group installation () 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Type of protection () Surge protection
Screw thread (General) M3
Output name (Input data) AC output
(Approvals/conformities) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Connection name (General) Load circuit
Cooling time (Input data) 20 min. (for auto reset)
(Output data load output) 2 A (24 V, DC13)
Input name (Device supply) Control input right/left
Stripping length (General) 8 mm
Surge current (Input data) 100 A (t = 10 ms)
Connection method (General) Screw connection
Depth (Key Commercial Data) 113.7 mm
Width (Key Commercial Data) 22.5 mm
(Standards and Regulations)  II (2) D [Ex t] [Ex p]
Height (Key Commercial Data) 106.6 mm
Leakage current (Input data) 0 mA
Mains frequency (Input data) 50/60 Hz
(Insulation characteristics)  II (2) D [Ex t] [Ex p]
Degree of pollution (UL data) 2
Rated surge voltage (UL data) 6 kV
Residual voltage (Input data) < 0.5 V
Note (Output data load output) Confirmation: floating change-over contact, signal contact
Overvoltage category (UL data) III
Control supply voltage range () 92 V AC ... 253 V AC
Load current range (Input data) 1.5 A ... 9 A (see to derating)
Switching level (Device supply) < 5 V DC (For EMERGENCY STOP)
Type of protection (Input data) Surge protection
ATEX (Standards and Regulations)  II (2) G [Ex e] [Ex d] [Ex px]
ATEX (Insulation characteristics)  II (2) G [Ex e] [Ex d] [Ex px]
Rated control supply current IS () 4 mA
Rated insulation voltage (UL data) 500 V
China RoHS (Approvals/conformities) Environmentally Friendly Use Period = 50
REACh SVHC (Approvals/conformities) Lead 7439-92-1
Switching threshold (Device supply) 44 V AC (“0” signal)
Operating voltage range (Input data) 42 V AC ... 550 V AC
Weight per Piece (excluding packing) 223.150 g
Conductor cross section AWG (General) 24 ... 14
Indication (Output data reply output) Red LED
Output name (Output data load output) Acknowledge output
Typical response time (Device supply) < 35 ms
Typical turn-off time (Device supply) < 80 ms
Contact type (Output data load output) 1 PDT
Conductor cross section solid (General) 0.2 mm² ... 2.5 mm²
Rated operating current Ie (Input data) 9 A (AC-51)
Rated operating voltage Ue (Input data) 500 V AC
Designation (Insulation characteristics) Standards/regulations
Mounting type (Output data reply output) DIN rail mounting
Triggering voltage range (Device supply) 92 V AC ... 253 V AC
Operating mode (Output data reply output) 100% operating factor
Status display (Output data reply output) Yellow LED
Conductor cross section flexible (General) 0.2 mm² ... 2.5 mm²
Degree of protection (Key Commercial Data) IP20
Rated actuating current IC (Device supply) 7 mA
Rated actuating voltage UC (Device supply) 230 V AC
Rated control circuit supply voltage US () 230 V AC
UL certificate (Standards and Regulations) NLDX.E228652
Mounting position (Output data reply output) Vertical (horizontal DIN rail)
Switching frequency (Output data reply output) ≤ 2 Hz (Load-dependent)
Assembly instructions (Output data reply output) Can be aligned with spacing = 20 mm
Standards/regulations (Insulation characteristics) DIN EN 50178
Maximum power dissipation (Output data reply output) 16.1 W
Minimum power dissipation (Output data reply output) 2.6 W
Operating voltage display (Output data reply output) Green LED
Ambient temperature (operation) (Key Commercial Data) -25 °C ... 70 °C (observe derating)
Category acc. to EN ISO 13849 (Standards and Regulations) ≤ 3 (Safe shutdown)
EU-type examination certificate (Standards and Regulations) PTB 07 ATEX 3145
Ambient temperature (storage/transport) (Key Commercial Data) -40 °C ... 80 °C
Trigger characteristic in acc. with IEC 60947-4-2 (Input data) Class 10A
Performance level according to ISO 13849 (Standards and Regulations) ≤ e (Safe shutdown)
Switching capacity according to IEC 60947-5-1 (Output data load output) 3 A (230 V, AC15)
Safety Integrity Level according to IEC 61508 (Standards and Regulations) ≤ 3 (Safe shutdown)

Popis produktu

Inverse contactor. semicon. three-phase "4 in 1" with 230 V AC input, corr. Exit 9 A, with func. Emergency stop and shutdown. by envelope. fit.
Kľúčové vlastnosti
  • Priemyselná kvalita
  • V súlade s RoHS
  • Certifikácia CE
  • 1-ročná záruka

Dokumenty k produktu

Dátový list

Technické špecifikácie a údaje o výkone

Používateľská príručka

Návod na inštaláciu a obsluhu

Top